NPG / GMG · deep-cycle GEL electrolyte

GEL Lead-Acid Battery

Pure GEL batteries for standby and repeated cyclic duty, spanning 6V/12V NPG blocks and 2V GMG stationary cells.

CATALOGUE MANUFACTURING SOURCEGuangdong Zhicheng Champion Group Co., Ltd.Product selection and export inquiry contact: Sodium Energy Systems
Champion NPG and GMG pure GEL lead-acid battery product families
CROPPED PRODUCT IMAGE · CHAMPION LEAD-ACID BATTERY CATALOGUE 2023
NPG RANGE6V / 12V, 18–250Ah
GMG RANGE2V, 150–1000Ah
CYCLE STATEMENT500 cycles at 80% DOD
TEMPERATURE STATEMENT−35°C to 45°C

Product range

Models, ratings and installation differences

NPG Series is catalogue-described with pure GEL electrolyte, heavy-duty grids, deep-discharge recovery, 500 cycles at 80% DOD and a 12-year floating design-life statement. Its 12V range covers 18–250Ah, plus a 6V 225Ah model. GMG uses 2V cells from 150Ah to 1000Ah with a 15-year catalogue design-life statement for larger stationary banks.

Model comparison

Compare the ratings that affect your installation.

These figures are transcribed from the catalogue revision identified with the product image. Request the current model datasheet before approval or purchase.

Series / modelRatingSize L×W×H (mm)Weight3-hour capacity10-hour capacity100-hour capacity
NPG / NP55-12-G12V 55Ah229 × 138 × 21419kg42Ah55Ah60Ah
NPG / NP100-12-G12V 100Ah306 × 168 × 21432.5kg75Ah99Ah105Ah
NPG / NP200-12-G12V 200Ah520 × 238 × 22366kg155Ah200Ah220Ah
GMG / GM200-2-G2V 200Ah173 × 111 × 32915kg150Ah200Ah220Ah
GMG / GM600-2-G2V 600Ah301 × 175 × 33143kg450Ah600Ah620Ah
GMG / GM1000-2-G2V 1000Ah475 × 175 × 32869.2kg750Ah1000Ah1020Ah

Product selection

Load, charger and installation details

Available project information is enough for an initial model shortlist and document response.

01

Choose block or cell architecture

NPG 12V blocks simplify smaller banks; GMG 2V cells support larger strings and need rack and connector planning.

02

Define cycling severity

State DOD, cycles per day, partial-state-of-charge periods and recharge time.

03

Confirm charge voltage

The catalogue lists 2.40–2.45V per cell for cycle service and 2.25–2.30V per cell for float service at 25°C.

Typical applications

Applications for this battery family

Product matching is based on the equipment, duty cycle and installation conditions supplied with the inquiry.

01

Solar and photovoltaic

Use daily load, autonomy and recharge energy to size the bank.

02

Telecom and UPS

Confirm float settings, outage runtime, cabinet temperature and space.

03

Remote standby

Account for service interval, transport, temperature and time at partial state of charge.

Commercial information

Current purchasing details for the selected model

Availability, documents and commercial terms are provided against the requested model, quantity and destination.

01MOQ and sample availability02Current production lead time03Model datasheet and available certificates04Packing, shipment and Incoterm options05Warranty basis and claim process06OEM branding or configuration options

For an accurate quote

Send these details if available

  1. 01Required voltage, bank Ah and proposed series/parallel layout
  2. 02Discharge duration, DOD and recharge source
  3. 03Cycle or float charger voltage and temperature compensation
  4. 04Rack, inter-cell connectors, enclosure and service access
  5. 05Current exact-model capacity, cycle and UL documentation
Deep-Cycle Lead-Acid Battery→OPzV / OPzS Tubular Battery→Lead-Acid Product Family→

Product FAQ

Questions buyers ask before ordering

We will confirm current availability, documents and commercial terms for the exact model you select.

How is GEL different from AGM?+

The electrolyte and internal construction differ. Selection should be based on duty, charge profile, temperature and exact model data rather than a general claim that one is always better.

What life claims are in the catalogue?+

NPG is described with up to 12 years and GMG up to 15 years design life. Conditions and exact-model support must be confirmed.

Can these batteries operate horizontally?+

The catalogue describes sealed batteries as operable vertically or horizontally. Installation instructions for the exact model still govern.

What temperature range is stated?+

The catalogue states −35°C to 45°C for the GEL family.

Why do capacity values change by discharge time?+

Lead-acid batteries deliver less Ah at higher discharge rates. Use the rate closest to the actual runtime.

Product inquiry

Request product data, availability or a quotation.

Send the available application, voltage, load, runtime, installation space, quantity and destination.